SABIX® IBS 610 FRNC

Halogen-free, flame retardant Interbus-S cable

Marking for SABIX IBS 610 FRNC 66103221: SAB BRÖCKSKES · D-VIERSEN · SABIX IBS 610 FRNC 3 x 2 x 0,22 mm² CE

Marking for SABIX IBS 610 FRNC 66103221: SAB BRÖCKSKES · D-VIERSEN · SABIX IBS 610 FRNC 3 x 2 x 0,22 mm² CE

Application

In addition to being halogen-free, this cable is also flame-retardant. The INTERBUS-S cable is stranded in pairs and free of hazardous substances in accordance with the RoHS directive of the European Union. The cable is used particularly in manufacturing, transport and storage technology. 

Outstanding features

  • halogen-free
  • no flame propagation
  • flame retardant and self-extinguishing
  • good weather resistance

Construction

Conductor

bare copper strands with reference to VDE 0812

Insulation

SABIX®

Colour code

with reference to DIN 47100

Stranding

twisted to pairs and pairs together

Wrapping

PETP foil

Screen

tinned copper braiding

Sheath material

SABIX®

Sheath colour

redlilac (RAL 4001)

Conductor

bare copper strands with reference to VDE 0812

Insulation

SABIX®

Colour code

with reference to DIN 47100

Stranding

twisted to pairs and pairs together

Wrapping

PETP foil

Screen

tinned copper braiding

Sheath material

SABIX®

Sheath colour

redlilac (RAL 4001)

Technical data

Peak operating voltage

max. 350 V

Testing voltage

core/core: 1000V

core/screen: 1000V

Min. bending radius

7,5 x d

Temperature range

fixed laying: -40/+85 °C

flexible application: -30/+85 °C

Halogen-free

acc. to IEC 60754-1 + VDE 0482-754-1

Flame propagation

no flame propagation
acc. to IEC 60332-3-24 + IEC 60332-3-25  category C resp. D

Fire performance

flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Corrosiveness of conflagration gases

in compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases

Smoke density

acc. to IEC 61034 + VDE 0482-1034

Characteristic impedance at 0.064 MHz

120 Ω ± 20%

Characteristic impedance at > 1 MHz

100 Ω ± 15 Ω

Flexibility

good

Application in cable tracks

not recommended

Weather resistance

good

Direct Burial

not suitable

Absence of harmful substances

acc. to RoHS directive of the European Union

Peak operating voltage

max. 350 V

Testing voltage

core/core: 1000V

core/screen: 1000V

Min. bending radius

7,5 x d

Temperature range

fixed laying: -40/+85 °C

flexible application: -30/+85 °C

Halogen-free

acc. to IEC 60754-1 + VDE 0482-754-1

Flame propagation

no flame propagation
acc. to IEC 60332-3-24 + IEC 60332-3-25  category C resp. D

Fire performance

flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2

Corrosiveness of conflagration gases

in compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases

Smoke density

acc. to IEC 61034 + VDE 0482-1034

Characteristic impedance at 0.064 MHz

120 Ω ± 20%

Characteristic impedance at > 1 MHz

100 Ω ± 15 Ω

Flexibility

good

Application in cable tracks

not recommended

Weather resistance

good

Direct Burial

not suitable

Absence of harmful substances

acc. to RoHS directive of the European Union

Dimensions

item no. Type Dimension Outer-ø ± 10% Copper figure Cable weight ≈
L66103221Remote bus cable3 x 2 x 0,22 mm²7 mm31,3 kg/km62 kg/km Send inquiry
L66106221Installation remote bus cable3 x 2 x 0,22 mm² + 3 x 1,00 mm²7,9 mm62 kg/km94 kg/km Send inquiry
item no.
Type
Dimension
Outer-ø ± 10%
Copper figure
Cable weight ≈
L66103221
Remote bus cable
3 x 2 x 0,22 mm²
7 mm
31,3 kg/km
62 kg/km
L66106221
Installation remote bus cable
3 x 2 x 0,22 mm² + 3 x 1,00 mm²
7,9 mm
62 kg/km
94 kg/km

Other dimensions and colours are possible on request.

Highly flexible cables according to your special requirements

Family business for construction and production since 1947

Please send us your inquiry
+49 (0)2162 898-0
Monday to Thursday, 7.30–16.30
Friday, 07.30–15.00