Application
SiAF/BiAF is silicone insulated strands that are heat resistant and halogen-free. Moreover, they are made for flexible applications for internal wiring of lamps, heating appliances, switchboard plants and distributors in industries such as smelteries, steelworks, and hot-rolling mills, industrial oven and textile machine construction, lamp, illumination, and electric industries, wood working and paper processing industries.
Outstanding features
- halogen-free
- flexible at low temperatures
- heat resistant
Additional information
Colour code for single conductors:
0 = green-yellow 4 = grey
1 = blue 5 = white
2 = black 6 = reddish brown
3 = brown 7 = red
Construction
Conductor | tinned copper strands acc. to IEC 60228, VDE 0295, class 5 |
---|---|
Insulation | Besilen® EI2 acc. to EN 50363-1 + VDE 0207-363-1 |
tinned copper strands acc. to IEC 60228, VDE 0295, class 5
Besilen® EI2 acc. to EN 50363-1 + VDE 0207-363-1
Technical data
Nominal voltage | Uo/U 300/500 V |
---|---|
Testing voltage | 2000 V |
Min. bending radius | 7,5 x d |
Radiation resistance | 2 x 10^7 cJ/kg |
Temperature range | fixed laying: -40/+180°C flexible application: -25/+180°C short-time use: +250°C |
Halogen-free | acc. to IEC 60754-1 + VDE 0482-754-1 |
Fire performance | flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2 |
Corrosiveness of conflagration gases | IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases |
Chem. resistance | see "Technical Data" - Chemical resistance |
Weather resistance | very good |
Absence of harmful substances | acc. to RoHS directive of the European Union |
Uo/U 300/500 V
2000 V
7,5 x d
2 x 10^7 cJ/kg
fixed laying: -40/+180°C
flexible application: -25/+180°C
short-time use: +250°C
acc. to IEC 60754-1 + VDE 0482-754-1
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2
IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases
see "Technical Data" - Chemical resistance
very good
acc. to RoHS directive of the European Union
Dimensions
item no. |
Nominal cross section |
Largest single wire-ø | Copper figure | Cable weight ≈ | Outer-ø ± 5% | |
---|---|---|---|---|---|---|
L0113002…* | 0,25 mm² | 0,16 mm | 2,4 kg/km | 5 kg/km | 1,7 mm | Send inquiry |
L0113003…* | 0,34 mm² | 0,26 mm | 3,3 kg/km | 6 kg/km | 1,8 mm | Send inquiry |
L0113005…* | 0,5 mm² | 0,21 mm | 4,8 kg/km | 8 kg/km | 1,9 mm | Send inquiry |
L0113007…* | 0,75 mm² | 0,21 mm | 7,2 kg/km | 10 kg/km | 2,2 mm | Send inquiry |
L0113010…* | 1 mm² | 0,21 mm | 9,6 kg/km | 13 kg/km | 2,3 mm | Send inquiry |
L0113015…* | 1,5 mm² | 0,26 mm | 14,4 kg/km | 18 kg/km | 2,8 mm | Send inquiry |
L0113025…* | 2,5 mm² | 0,26 mm | 24 kg/km | 29 kg/km | 3,4 mm | Send inquiry |
L0113040…* | 4 mm² | 0,31 mm | 38,4 kg/km | 44 kg/km | 4 mm | Send inquiry |
L0113060…* | 6 mm² | 0,31 mm | 57,6 kg/km | 62 kg/km | 4,5 mm | Send inquiry |
L0113100…* | 10 mm² | 0,41 mm | 96 kg/km | 107 kg/km | 6,1 mm | Send inquiry |
L0113160…* | 16 mm² | 0,41 mm | 153,6 kg/km | 167 kg/km | 7,5 mm | Send inquiry |
L0113250…* | 25 mm² | 0,41 mm | 240 kg/km | 271 kg/km | 9,3 mm | Send inquiry |
L0113350…* | 35 mm² | 0,41 mm | 336 kg/km | 376 kg/km | 10,7 mm | Send inquiry |
L0113500…* | 50 mm² | 0,41 mm | 480 kg/km | 523 kg/km | 12,3 mm | Send inquiry |
L0113700…* | 70 mm² | 0,41 mm | 672 kg/km | 713 kg/km | 14,6 mm | Send inquiry |
L0113950…* | 95 mm² | 0,51 mm | 912 kg/km | 961 kg/km | 17,5 mm | Send inquiry |
L0113120…* | 120 mm² | 0,51 mm | 1152 kg/km | 1177 kg/km | 19 mm | Send inquiry |
L0113150…* | 150 mm² | 0,51 mm | 1440 kg/km | 1462 kg/km | 20,9 mm | Send inquiry |
L0113185…* | 185 mm² | 0,51 mm | 1776 kg/km | 1785 kg/km | 23 mm | Send inquiry |
L0113240…* | 240 mm² | 0,51 mm | 2304 kg/km | 2404 kg/km | 26,9 mm | Send inquiry |
L0113300…* | 300 mm² | 0,51 mm | 2880 kg/km | 2998 kg/km | 30 mm | Send inquiry |
section
wire-ø
Other dimensions and colours are possible on request.