Application
The fire resistant & fire retardant cable with silver-plated strands, good solderability is recommended for use in internal wiring at high ambient temperatures in protected rooms.
The core cable is also available with tinned copper strands on request.
Outstanding features
- halogen-free
- high temperature resistant
- Fire retardant and self-extinguishing acc. to IEC 60332-1-2 + DIN EN 60332-1-2
- flexible
- VDE-Reg.-No. 7088
- good solderability
Additional information
* Colour code for the single wire/core line can be selected as follows:
Colour code | Colour | Colour code | Colour |
01 = | black | 06 = | green |
02 = | blue | 07 = | purple |
03 = | brown | 08 = | white |
04 = | grey | 16 = | gentian blue |
05 = | yellow | 27 = | green/yellow |
Color code for single cores/leads
Construction
Conductor | silver-plated copper strands, fine wires acc. to IEC 60228, VDE 0295, class 5 |
---|---|
Insulation | SABIX® |
Colour code | see table*additional information |
silver-plated copper strands, fine wires acc. to IEC 60228, VDE 0295, class 5
SABIX®
see table*additional information
Technical data
Nominal voltage | Uo/U 300/500 V |
---|---|
Testing voltage | 2000 V |
Min. bending radius | 7,5 x d For one single bend: 5 x d |
Temperature range | fixed laying: -40/+220 °C flexible application: -25/+220 °C |
Halogen-free | acc. to IEC 60754-1 + VDE 0482-754-1 |
Fire performance | flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2 |
Corrosiveness of conflagration gases | in compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases |
Absence of harmful substances | acc. to RoHS directive of the European Union |
Uo/U 300/500 V
2000 V
7,5 x d
For one single bend:
5 x d
fixed laying: -40/+220 °C
flexible application: -25/+220 °C
acc. to IEC 60754-1 + VDE 0482-754-1
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2
in compliance with IEC 60754-2 + VDE 0482-754-2 - no development of corrosive conflagration gases
acc. to RoHS directive of the European Union
Dimensions
item no. |
Nominal cross section |
Largest single wire-ø | Outer-ø ± 5% | Copper figure | Cable weight ≈ | |
---|---|---|---|---|---|---|
L7101 .. 25* | 0,25 mm² | 0,16 mm | 2,3 mm | 2,4 kg/km | 7 kg/km | Send inquiry |
L7101 .. 34* | 0,34 mm² | 0,16 mm | 2,4 mm | 3,3 kg/km | 8 kg/km | Send inquiry |
L7101 .. 50* | 0,5 mm² | 0,21 mm | 2,5 mm | 4,8 kg/km | 10 kg/km | Send inquiry |
L7101 .. 75* | 0,75 mm² | 0,21 mm | 2,8 mm | 7,2 kg/km | 13 kg/km | Send inquiry |
L7101 .. 80* | 1 mm² | 0,21 mm | 2,9 mm | 9,6 kg/km | 15 kg/km | Send inquiry |
L7101 .. 82* | 1,5 mm² | 0,26 mm | 3,4 mm | 14,4 kg/km | 21 kg/km | Send inquiry |
L7101 .. 84* | 2,5 mm² | 0,26 mm | 4 mm | 24 kg/km | 32 kg/km | Send inquiry |
L7101 .. 86* | 4 mm² | 0,31 mm | 4,6 mm | 38,4 kg/km | 48 kg/km | Send inquiry |
L7101 .. 87* | 6 mm² | 0,31 mm | 5,1 mm | 57,6 kg/km | 67 kg/km | Send inquiry |
L7101 .. 88* | 10 mm² | 0,41 mm | 7,4 mm | 96 kg/km | 121 kg/km | Send inquiry |
L7101 .. 89* | 16 mm² | 0,41 mm | 8,4 mm | 153,6 kg/km | 176 kg/km | Send inquiry |
L7101 .. 90* | 25 mm² | 0,41 mm | 10,3 mm | 240 kg/km | 283 kg/km | Send inquiry |
L7101 .. 91* | 35 mm² | 0,41 mm | 11,5 mm | 336 kg/km | 385 kg/km | Send inquiry |
L7101 .. 92* | 50 mm² | 0,41 mm | 14,2 mm | 480 kg/km | 549 kg/km | Send inquiry |
L7101 .. 93* | 70 mm² | 0,41 mm | 15,2 mm | 672 kg/km | 736 kg/km | Send inquiry |
L7101 .. 94* | 95 mm² | 0,51 mm | 18,6 mm | 912 kg/km | 1009 kg/km | Send inquiry |
L7101 .. 95* | 120 mm² | 0,51 mm | 20,1 mm | 1152 kg/km | 1214 kg/km | Send inquiry |
L7101 .. 96* | 150 mm² | 0,51 mm | 22,2 mm | 1440 kg/km | 1511 kg/km | Send inquiry |
L7101 .. 97* | 185 mm² | 0,51 mm | 23,6 mm | 1776 kg/km | 1827 kg/km | Send inquiry |
L7101 .. 98* | 240 mm² | 0,51 mm | 27,3 mm | 2304 kg/km | 2457 kg/km | Send inquiry |
L7101 .. 99* | 300 mm² | 0,51 mm | 30,4 mm | 2880 kg/km | 3062 kg/km | Send inquiry |
section
wire-ø
Other dimensions and colours are possible on request.