S 670
PUR hybrid field bus control cable, suitable for cable tracks with UL recognition, CSA approval
Marking for S 670 06701604: SAB BRÖCKSKES · D-VIERSEN · S 670 4 x 1,5 mm² + 2 POF UL AWM Style 21060 80°C 600V CSA AWM I/II A/B 80°C 600V FT1 FT2 CE
Application
This cable is a PUR hybrid field bus control cable, which is also suitable for cable tracks. It has fibre optic cables and copper wires. Due to its polyurethane outer sheath, it has very good chemical resistance to acids, alkalis, solvents, hydraulic fluids and oils. Furthermore, it is suitable for continuous bending stress.
Outstanding features
- UL recognized, CSA approved
- suitable for cable tracks
- flame retardant and self-extinguishing
- very good oil resistance
- very good chemical resistance
- with optical waveguide and copper conductors
Additional information
optical waveguide + copper conductors!
Construction
Conductor | bare copper strands, extra fine wires |
---|---|
Insulation | PVC, TI2 acc. to EN 50363-3 |
Colour code | black cores with consecutive numbers acc. to EN 50334 + VDE 0293-334, green-yellow earth wire from 3 cores |
Optical waveguide | POF (polymeric optical fibres) |
Colour code POF | black |
Stranding | cores and POF in specially adjusted layering |
Wrapping | non-woven tape |
Sheath material | PUR, TMPU acc. to EN 50363-10-2 + VDE 0207-363-10-2 with matt surface |
Sheath colour | redlilac (RAL 4001) |
bare copper strands, extra fine wires
PVC, TI2 acc. to EN 50363-3
black cores with consecutive numbers acc. to EN 50334 + VDE 0293-334, green-yellow earth wire from 3 cores
POF (polymeric optical fibres)
black
cores and POF in specially adjusted layering
non-woven tape
PUR, TMPU acc. to EN 50363-10-2 + VDE 0207-363-10-2 with matt surface
redlilac (RAL 4001)
Technical data
Nominal voltage | Uo/U 300/500 V |
---|---|
Voltage UL/CSA | 600 V |
Testing voltage | core/core 3000 V |
Min. bending radius | fixed installation: 4 x d flexible application: 7,5 x d continuously flexible: 10 x d |
Temperature range | fixed laying: -40/+70°C flexible application: +5/+70°C UL/CSA: up to +80°C |
Fire performance | flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2 |
Oil resistance | very good - acc. to EN 50363-10-2 + VDE 0207-363-10-2 |
Attenuation POF measured at 650nm: | max. 10dBm/20m |
Diameter | POF: centre 900/1000 μm outside 2,2 mm |
UL Style | 21060 |
Absence of harmful substances | acc. to RoHS directive of the European Union |
Uo/U 300/500 V
600 V
core/core 3000 V
fixed installation: 4 x d
flexible application: 7,5 x d
continuously flexible: 10 x d
fixed laying: -40/+70°C
flexible application: +5/+70°C
UL/CSA: up to +80°C
flame retardant and self-extinguishing acc. to IEC 60332-1-2 + VDE 0482-332-1-2
very good - acc. to EN 50363-10-2 + VDE 0207-363-10-2
max. 10dBm/20m
POF:
centre 900/1000 μm
outside 2,2 mm
21060
acc. to RoHS directive of the European Union
Dimensions
item no. | Dimension |
Largest single wire-ø | Outer-ø ± 5% | Copper figure | Cable weight ≈ | |
---|---|---|---|---|---|---|
L06700415 | 4 x 1,50 mm² | 0,16 mm | 10,0 mm | 57,6 kg/km | 132 kg/km | Send inquiry |
L06700515 | 5 x 1,50 mm² | 0,16 mm | 10,6 mm | 72,0 kg/km | 156 kg/km | Send inquiry |
L06700425 | 4 x 2,50 mm² | 0,16 mm | 12,2 mm | 96,0 kg/km | 197 kg/km | Send inquiry |
L06700525 | 5 x 2,50 mm² | 0,16 mm | 13,1 mm | 120,0 kg/km | 239 kg/km | Send inquiry |
wire-ø
Other dimensions and colours are possible on request.