Application
This cable is a Profinet type B cable, which is suitable for flexible use. Its inner sheath is made of thermoplastic material and its outer sheath of SABIX®. Industrial Ethernet is a young and very fast developing network technology. SAB has developed this Profinet cable especially for the automation industry.
Additional information
also possible as harnessed cable with M12 or RJ 45 plug
Construction
Dimension | 2 x 2 x 22 AWG |
---|---|
Conductor | bare copper strands, fine wires acc. to VDE 0812 |
Insulation | PE, L/MD acc. to EN 50290-2-23 |
Colour code | blue, yellow, white, orange |
Stranding | in layers |
Wrapping | PETP-foil |
Inner sheath | thermoplastic material |
Screen | alu foil and tinned copper braiding |
Wrapping | non-woven tape |
Sheath material | SABIX® |
Sheath colour | green (similar RAL 6018) |
2 x 2 x 22 AWG
bare copper strands, fine wires acc. to VDE 0812
PE, L/MD acc. to EN 50290-2-23
blue, yellow, white, orange
in layers
PETP-foil
thermoplastic material
alu foil and tinned copper braiding
non-woven tape
SABIX®
green (similar RAL 6018)
Technical data
Peak operating voltage | VDE: max 350 V |
---|---|
Testing voltage | core/core: 1500 V core/screen: 1200 V |
Min. bending radius | fixed laying: 5 x d flexible application: 12 x d |
Temperature range | VDE fixed laying: -30/+70 °C VDE flexible application: -20/+70 °C |
Halogen-free | acc. to IEC 60754-1 + VDE 0482-754-1 |
Characteristic impedance | 100Ω ± 5Ω, fulfils the electrical and transmission requirements with high frequency acc. to EN 50288-2-2 + VDE 0819-2-2 (CAT 5 acc. to EN 50173-1) |
Application | suitable for EtherCAT and EtherNET/IP applications |
Absence of harmful substances | acc. to RoHS directive of the European Union |
VDE: max 350 V
core/core: 1500 V
core/screen: 1200 V
fixed laying: 5 x d
flexible application: 12 x d
VDE fixed laying: -30/+70 °C
VDE flexible application: -20/+70 °C
acc. to IEC 60754-1 + VDE 0482-754-1
100Ω ± 5Ω, fulfils the electrical and transmission requirements with high frequency
acc. to EN 50288-2-2 + VDE 0819-2-2 (CAT 5 acc. to EN 50173-1)
suitable for EtherCAT and EtherNET/IP applications
acc. to RoHS directive of the European Union
Dimensions
item no. | Dimension | max. core-ø | Outer-ø ± 5% | Copper figure | Cable weight ≈ |
Ohmic resistance at 20°C acc. to VDE 0812 max. Ω/km | |
---|---|---|---|---|---|---|---|
L06602202 | 2 x 2 x 22 AWG | 1,55 mm | 36,2 kg/km | 67 kg/km | 55.4 | Send inquiry |
at 20°C acc. to VDE 0812
max. Ω/km
Other dimensions and colours are possible on request.