GP 400 Sy

400 Hz Ground Power supply cable - Symmetrical

Marking example: SAB BRÖCKSKES · D-VIERSEN ·
GP 400 Sy 7x35,0mm²+6x3x1,0mm²
3400-7213 CE and continuous meter marking

Marking example: SAB BRÖCKSKES · D-VIERSEN · GP 400 Sy 7x35,0mm²+6x3x1,0mm² 3400-7213 CE and continuous meter marking

Application

For use as fixed installation cable in 400 Hz systems, e.g. between 400 Hz generator and cable dispenser.

Outstanding features

  • reduced outside diameter

Additional information

Also available with 24 control cores!

Construction

Conductor

tinned copper strands

Insulation

35,0mm²: PVC

1,0mm²: SABIX®

Colour code

control cores: black with numbers 1-18

neutral core: blue

phase core: white, brown, black

(two conductors of the same colour form the phase)

Stranding

phase conductor concentrically around the neutral conductor, control conductors as triple in the fillers

Sheath material

PVC

Sheath colour

orange

Conductor

tinned copper strands

Insulation

35,0mm²: PVC

1,0mm²: SABIX®

Colour code

control cores: black with numbers 1-18

neutral core: blue

phase core: white, brown, black

(two conductors of the same colour form the phase)

Stranding

phase conductor concentrically around the neutral conductor, control conductors as triple in the fillers

Sheath material

PVC

Sheath colour

orange

Technical data

Nominal Voltage

Uo/U 0,6/1 kV

Testing Voltage

core/core 4000 V AC

Min. bending radius

fixed laying: 4 x d

flexible application : 8 x d

Temperature range

fixed laying: -40/+70°C

flexible application: +5/+70°C

Absence of harmful substances

acc. to RoHS directive of the European Union

Nominal Voltage

Uo/U 0,6/1 kV

Testing Voltage

core/core 4000 V AC

Min. bending radius

fixed laying: 4 x d

flexible application : 8 x d

Temperature range

fixed laying: -40/+70°C

flexible application: +5/+70°C

Absence of harmful substances

acc. to RoHS directive of the European Union

Dimensions

item no. No. of cores x
cross section
Approx. outer-ø Copper figure Cable weight ≈ Ohmic resistance
at 20°C max.
Voltage drop Outer-ø ± 5%
L340072107 x 35,0 mm²37,0 mm2352,0 kg/km3003 kg/km0,554 Ω/km1,108 [mV/(A*m)]37 Send inquiry
L340072137 x 35,0 mm² + 6 x 3 x 1,0 mm²37,0 mm2524,8 kg/km3125 kg/km0,554 / 19,5 Ω/km1,108 / 39,0 [mV/(A*m)]37 Send inquiry
item no.
No. of cores x
cross section
Approx. outer-ø
Copper figure
Cable weight ≈
Ohmic resistance
at 20°C max.
Voltage drop
Outer-ø ± 5%
L34007210
7 x 35,0 mm²
37,0 mm
2352,0 kg/km
3003 kg/km
0,554 Ω/km
1,108 [mV/(A*m)]
37
L34007213
7 x 35,0 mm² + 6 x 3 x 1,0 mm²
37,0 mm
2524,8 kg/km
3125 kg/km
0,554 / 19,5 Ω/km
1,108 / 39,0 [mV/(A*m)]
37

Other dimensions and colours are possible on request.

Highly flexible cables according to your special requirements

Family business for construction and production since 1947

Please send us your inquiry
+49 (0)2162 898-0
Monday to Thursday, 7.30–16.30
Friday, 07.30–15.00