The cables manufactured by SAB Bröckskes are only appropriate for the transmission of electric energy for supply and signalling purposes.
First of all the valid construction and installation prescriptions for the corresponding machine or equipment has to be observed. The valid
VDE prescription 0100 can be regarded as base. Furthermore, the following security advice has to be observed for the use of cables.
The safe application is described under„security requirements” and „boundary conditions”.
For each cable type you can find under „technical data” information on fields that can also be found under the following standards.
Among others these are:
Nominal voltage, Peak operating voltage | HD 516 |
Test voltage | VDE 0250 T1; EN 50525-1 as well as relevant cable standards |
Minimum bending radius | HD 516 |
Temperature range | HD 516 |
Fire performance | standards of series IEC 60332 as well as relevant cable standards |
Resistances | EN 60811-404 as well as relevant cable standards |
Under „security requirements” you will find information on fields that can also be found under the following standards.
Among others these are.:
Basic requirements | HD 516 Pos. 4. |
General requirements | HD 516 Pos. 4.2 |
Current-carrying capacity for undisturbed service | VDE 0298-4 Pos. 5 |
Operating conditions | VDE 0298-4 Pos. 5.3.1 |
Ambient conditions | VDE 0298-4 Pos. 5.3.3 |
Requirements for fixed laying | HD 516 Pos 4.3 |
Requirements for flexible cables | HD 516 Pos. 4.4 |
Under „boundary conditions” you will find information on fields that can also be found under the following standards.
Among others these are.:
Operating conditions | HD 516 Pos. 5 | |
Voltage | HD 516 S2 Pos. 5.1 | |
Current-carrying capacity | HD 516 Pos. 5.2 | |
Capacity, cables with a nominal voltage up to 1000 V and heat resistant cables | VDE 0298 T4 table 11 | |
Conversion factors for deviating ambient temperatures | VDE 0298 T4 table 17 + 18 | |
Conversion factors for the accumulation on walls, in tubes and conduits, on the floor and at the ceiling | VDE 0298 T4 table 21 | |
Conversion factors for multi-core cables with conductor cross sections up to 10 mm² | VDE 0298-4 table 26 | |
Thermal influences | HD 516 Pos. 5.3 | |
Mechanical stress | HD 516 Pos. 5.4 | |
Tensile load | HD 516 Pos. 5.4.1 | |
Bending load | HD 516 Pos. 5.4.2 | |
Compression stress | HD 516 Pos. 5.4.3 | |
Torsional stress | HD 516 Pos. 5.4.4 | |
Compatibility | HD 516 Pos. 5.5 | |
Application in rooms and in the open air | HD 516 annex A | |
Stress classification | HD 516 annex B | |
Construction of strands | EN 60228 + VDE 60228 |
Besides the generally known technical rules,
please consider especially the following prescriptions for the application of our products
VDE… | 0100, 0105, 0106, 0108, 0110, 0113, 0116, 0165, 0166, 0170, 0171, 0271, 0298, 0700, 0720, 0727, 0730, 0737, 0740, 0745, 0750, 0800, 0804, 0805, 0839, 0860, 0891, 1000, etc. |
You will find under the individual item groups further instructions and the description of the special application possibilities of our cables.
Do you have any questions about our products? Your direct line to our experts! Contact